IRSST - Institut de recherche Robert-Sauvé en santé et en sécurité du travail

Benomyl (Pi)  

French name in the regulation: Benomyle (Pi)
CAS : 17804-35-2

Exposure Standards in RROHS regulation

Permissible exposure values (PEV)
ppm mg/m3 f/cc Notes
TWAEV - 1 - Pi
STEV - - - -
Ceiling - - - -
Carcinogenicity C3 Sensitizer D
Simple asphyxiantPercutaneous
Prohibited useProhibited recirculation
Minimum exposureExplosion hazard
Ototoxic

TWA adjustment for unusual work schedules

1C : No adjustment

CNESST – Toxicological Index Service

Consult REPTOX file: Benomyl(Pi)

Analysis:

Benomyle

Recommended method by the IRSST:
Method: NIOSH - 5601
Sampling device: OVS-2 tube with XAD-2 and glass fiber filter
Parameters:
Flow rate: 0,1-1,0 L/min
TWA sampling volume: 480 L
STEL sampling volume: -
Remarks: This substance is not analyzed by our laboratories. It might be possible that the analysis be performed by another laboratory. Please contact the IRSST before sampling. The aerosol phase might be underestimated because the efficiency of the sampling device does not match inhalable fraction definition. For more information, please contact the IRSST.
Principle: High performance liquid chromatography with UV detection (HPLC-UV)
NIOSH, Manual of Analytical Methods 5601, 4th ed., Organonitrogen pesticides, 1998.