IRSST - Institut de recherche Robert-Sauvé en santé et en sécurité du travail

Methyl ethyl ketone peroxide  

French name in the regulation: Peroxyde de méthyl éthyl cétone
CAS : 1338-23-4

Exposure Standards in RROHS regulation

Permissible exposure values (PEV)
ppm mg/m3 f/cc Notes
TWAEV - - - -
STEV - - - -
Ceiling 0,2 1,5 - -
Carcinogenicity Sensitizer
Simple asphyxiantPercutaneous
Prohibited useProhibited recirculation
Minimum exposureExplosion hazard
Ototoxic

TWA adjustment for unusual work schedules

1A : No adjustment

CNESST – Toxicological Index Service

Consult REPTOX file: Methyl ethyl ketone peroxide

Analysis:

Peroxyde de méthyl éthyl cétone

Recommended method by the IRSST:
Method: NIOSH - 3508
Sampling device: XAD-4 tube
Parameters:
Flow rate: 1 L/min
TWA sampling volume: 15 L
STEL sampling volume: -
Remarks: Substance is unstable at ambient temperature. Contact the IRSST before sampling.
Principle: High performance liquid chromatography with UV detection (HPLC-UV)
NIOSH Manual of Analytical Methods, 4th ed., Method 3508 : Methyl Ethyl Ketone Peroxide, 1994.